Non-Compliance detail


  
Summary
 
Licence number: 10693
Annual Return Start: 01 Apr 2015
Annual Return End: 31 Mar 2016
Date Received: 31 May 2016
 
Licence Condition numberType of non-complianceEPA actionsNo. of times occurred
O4.4 A portion of inflows less than 500L/s was discharged from point 4 without receiving degritting or biological treatment. During a storm the generator power was lost, causing a bypass of the biological treatment process. Mains power restored. Appropriate Action taken by licensee 1
O4.8 A portion of inflows was discharged from point 1 without receiving biological treatment and clarification. During upgrade works a UV lift pump automatically operated unexpectedly causing flows to bypass biological and clarification processes. Appropriate Action taken by licensee 1
M2.2 A sample was not analysed for pH or faecal coliforms. A sample was taken however the analysis was incorrectly prescribed resulting in pH and faecal coliforms not being analysed. Contract in place to ensure sampling carried out as required. Appropriate Action taken by licensee 2